Comment by MiroslavPokorny | original | 3rd Yandex Cloud Data Center Was Hit
[−]MiroslavPokorny · 2026-10-11 Sun 08:23 UTC · link
Datacenters are full of valuable computers and related equipment, but building the equivalent space under a mountain will cost a crazy amount.

Not worth paying 100x for the bunker to save 1x worth of computer stuff.

[−]walrus01 · 2026-10-11 Sun 08:26 UTC · link
Building any appreciable amount of compute capacity (on the scale of, let's say, a single large datacenter in northern VA) inside a mountain also becomes a huge heat rejection problem, since with the exception of the 0.00000000001% that leaves the facility as photons down a SM fiber cable, 100% of the energy consumed is turned into heat.

So you build your stuff inside a mountain and run a bunch of big ass liquid cooling loops to heat exchangers in the atmosphere outside the mountain. The requirement of the cooling system being out in the open air means it can also be hit by air strikes, an adversary doesn't need to penetrate the mountain, just take out its cooling.

You'd have to build a fully underground cooling system that goes to a nearby river (or huge lake) and use the cold water from that, which would get costly quick.

[−]testaccount28 · 2026-10-11 Sun 08:48 UTC · link
neat. why can't you put the heat in the mountain?
[−]walrus01 · 2026-10-11 Sun 08:54 UTC · link
For broadly the same reason that many years of heat from braking has heat-saturated the london underground.

https://www.google.com/search?client=firefox-b-d&q=london+un...

You could probably drill sideways into rocks and pump heat into the mountain for a certain period of time, but on a multi-month or year time scale, it would catch up with you after you had saturated it.

[−]martinjc · 2026-10-11 Sun 08:48 UTC · link
Pionen in sweden is a datacenter in a bunker. The Pirate Bay used to be hosted there.
[−]walrus01 · 2026-10-11 Sun 08:52 UTC · link
A few racks or even a couple of dozen racks could be called a datacenter, but nothing on any real scale. Enough to host important and niche things? Sure. I was referring more to like the size of what you might see in Quincy, WA.
[−]jeltz · 2026-10-11 Sun 09:58 UTC · link
Pionen is small but it is quite a bit bigger than "a couple of dozen racks". More like 100-200 if I recall correctly.
[−]martinjc · 2026-10-11 Sun 10:47 UTC · link
According to their site, Pionen has 1.5MW of cooling capacity https://swedendedicated.com/datacenter/
[−]efnx · 2026-10-11 Sun 08:51 UTC · link
So they want to build it in space. Trade one heat problem for another, but put it completely out of range (for most attackers).
[−]jltsiren · 2026-10-11 Sun 09:35 UTC · link
> You'd have to build a fully underground cooling system that goes to a nearby river (or huge lake) and use the cold water from that, which would get costly quick.

Helsinki gets its water from the 120 km Päijänne Water Tunnel, which cost €200-250 million (adjusted for inflation) to build. Peak flow is 10 m^3/s by gravity alone and up to 20 m^3/s with pumps, which should be enough to cool a 1 GW data center. You could increase the cost by 2x (because real wages have gone up), by another 2x (because middlemen have destroyed productivity), and by yet another 2x (because everything is more expensive in America), and it would still be pretty reasonable.

[−]Brybry · 2026-10-11 Sun 09:48 UTC · link
Iron Mountain does it but they used an existing limestone mine with a large water reservoir [1][2]

Edit: I guess the scale isn't comparable to a, for example, Google data center though.

[1] https://www.ironmountain.com/data-centers/colocation/our-dat...

[2] https://betterbuildingssolutioncenter.energy.gov/showcase-pr...

[−]killerstorm · 2026-10-11 Sun 12:17 UTC · link
They already run liquid cooling loops - compute density is way beyond what could circulate through air. Adding more pipes is probably trivial on the scale of datacenter expenses
[−]walrus01 · 2026-10-11 Sun 12:41 UTC · link
Liquid cooling loops don't solve the problem of needing to reject the heat to the atmosphere outside of the building. It just makes it more efficient to transport the heat. At the grossest possible definition, a datacenter of N megawatts on Y acres of land is going to emit the same amount of heat whether it's air cooled equipment or liquid is used to take the heat to the outdoor heat exchanging equipment. On the scale of any very large datacenter the heat exchanging equipment is visible from aerial photos (and from space), take a look at google maps for some of the largest hyperscalers for examples.
[−]jazzyjackson · 2026-10-11 Sun 08:28 UTC · link
The bunkers are already out there e.g. limestone mines in US, Italy,

https://www.datacenterknowledge.com/build-design/safer-under...

[−]walrus01 · 2026-10-11 Sun 08:34 UTC · link
Lots of people have built commercial, non-military, boutique scale stuff in hardened facilities, nobody I'm aware of has done it at scale. There's certainly money to be made from selling expensive "we put datacenter stuff deep down inside a mine" maybe to some weird enterprise and government customers, so the revenue per rack (or per theoretical 208V 30A circuit?) is probably a lot more than commodity colo. But I would very much like to see the aerial photos, if anyone can link them, to a claimed large scale underground or hardened datacenter.

It's a severe engineering challenge to hide massive heat exchangers on the scale of the datacenters built in the industrial area near Dulles (coordinate example: 38.9817915,-77.417775). Find those on a map and observe the scale of their cooling and generator systems and then try to find anything comparable that's been built underground.

[−]jazzyjackson · 2026-10-11 Sun 08:36 UTC · link
Agreed it’s small potatoes, and as a sibling mentions you will still have infrastructure exposed that poses a target to disable the data center, unless you were to drill geothermal and find an underground river to cool it.

Just wanted to make the point you don’t have to pay to excavate the cave :)

[−]IshKebab · 2026-10-11 Sun 09:06 UTC · link
That's probably just because there's not much demand for it, not because it's difficult.

There are mines with plenty of space in them, and heat removal can be done with water cooling. But who is going to pay 50% more for that when it isn't needed 99.99% of the time?

[−]walrus01 · 2026-10-11 Sun 09:08 UTC · link
Or when the same thing can be accomplished by putting nothing in a mine, but an approach as simple as having geographical diversity by paying for some 'normal' colo in Hillsboro, and more normal colo in northern VA on the other side of the continent, and duplicating your stuff between two facilities. Weird underground datacenters aren't exactly known for having a large number of competing on-net carriers.
[−]jeltz · 2026-10-11 Sun 10:09 UTC · link
> Weird underground datacenters aren't exactly known for having a large number of competing on-net carriers.

Huh? The ones I know of have plenty of connectivity. The real issue is your first, that people prefer to just put their stuff in two countries over paying premium for having their servers under ground.

[−]walrus01 · 2026-10-11 Sun 10:30 UTC · link
Your definition of connectivity may not be the same as mine, I'm referring to the number of facilities based carriers and those who ride on top of them you can get at major sites in Hillsboro. Facilities with peeringdb pages that have tons of on net carriers. Is there even an underground bunker colo that's big enough to rate its own peeringdb facility page?
[−]misiek08 · 2026-10-11 Sun 09:20 UTC · link
Germans hid plane engine factories underground with old (not so efficient) diesel generators running 24/7. 80 years ago, so the tech was leaner. Also they didn’t have issues with ventilation and even today if you don’t know where - you won’t see anything driving around.
[−]boelboel · 2026-10-11 Sun 09:59 UTC · link
There's some 200MW capacity (only 80MW is currently used or being built) data center in a mine near a fjord in Norway. The limiting factor for its capacity seems to be the capacity of the electricity net nearby (which you can just hit and the DC is useless). With how NIMBY Norwegians are there's no way it would ever get to a GW or more even if it might be both technically and economically feasible. That's just one project and can't be replicated anywhere else. It's just a massive advantage that above ground datacenters are relatively 'figured out' and similar everywhere.

edit: 61.9340107, 5.5084207 are the coordinates

[−]roenxi · 2026-10-11 Sun 08:32 UTC · link
It might be possible to do on the cheap; underground mines get decommissioned from time to time and could be repurposed as a data centre.

Although I personally would expect some sort of decentralisation option to be more effective. It's difficult to even theorise because we don't know exactly what sort of damage these strikes are doing and what countermeasures are already in place. If this strike has caught Yandex by surprise after almost 5 years of hot war then they really should hire a dude to check up on current events every so often. They must have some sort of contingency planning around a Ukrainian strike.

[−]microtonal · 2026-10-11 Sun 08:45 UTC · link
It's sad that we have moved away so far from the decentralized web from the 90s and the P2P boom of the 00s. Just like solar panels on every house as a source of energy are much harder to take out than just a few power plants, local P2P storage, messaging, source management, etc. are much harder to take out.

But yeah, the economic incentives are creating unicorns and centralizing compute/capital/etc.

[−]jeltz · 2026-10-11 Sun 10:11 UTC · link
The war in Ukraine had showed us that distributed power generation, like solar, and nuclear are most resilient. Nuclear because people do not dare striking the power plants.